UII UPDATE 552 | NOVEMBER 2026

Intelligence Update

Clearing the air on data center contamination

8 min read

Airborne contaminants in the data center, if left unchecked, pose a risk to both facilities and IT equipment, which can lead to more impactful outages. Yet the effects of dust and corrosive gases are rarely discussed in the context of resiliency, leading some industry experts to describe them as "the silent threat." The problem has become more acute as IT microelectronics have grown more delicate and more tightly integrated, while carrying higher electrical currents and operating at elevated temperatures.

Contaminant accumulation on surfaces can have a range of negative effects, including reduced cooling efficiency, performance degradation of IT and networking equipment and, in extreme cases, short circuits and electrical fires.

Problems caused by dust and corrosive gases are difficult to diagnose. A clogged heatsink, for example, might be interpreted as a fan failure, and an issue with an air filter can mask rubber particulates produced by a decomposing belt drive. The presence of certain gases may accelerate corrosion of exposed metal connections and wirings.

Resulting contact errors and short circuits within the IT equipment can be intermittent, which often leads to no trouble found diagnosis — a term used when a component is removed from service due to a reported fault or alarm, but no operational anomaly or defect is identified.

The primary tools to combat contamination are air filtration and humidity control, but other operational practices also help minimize risk. These include regular cleaning — yet cleaning itself also poses a risk to uptime, since all the equipment remains switched on during the process. For this reason, operators may be tempted to defer it.

This report outlines the risks posed by airborne contaminants and describes common approaches to monitoring, prevention and control.

How dust infiltrates a data center

Outdoor air is the main source of airborne particulate matter in a data center. To prevent contamination, data centers are typically designed to be almost airtight; all air entering the facility has to pass through filters. Many data centers are kept at positive pressure to prevent air seeping through any gaps in the perimeter.

However, staff movement, structural adjustments, maintenance tasks and IT refreshes can all introduce additional contaminants that must be dealt with on a regular basis.

The facility's susceptibility to dust is further influenced by location, design, construction and the choice of cooling system. Greater airflow velocities necessary to cool hotter processors can result in increased exposure to airborne contaminants.

The global standard for air quality typically referenced by data center operators, ASHRAE and equipment manufacturers is ISO 14644-1. It defines air quality classes in controlled environments based on the maximum allowable concentration of airborne particles per cubic meter of air. The higher the class, the fewer particles are permitted per volume of air at each size threshold — the allowed concentration differs tenfold between each class.

Data centers typically conform to Class 8 for air quality, one of the least restrictive (the most restrictive classes, 1-4, are used only in specialized cleanrooms). Class 8 allows for a maximum of 3,520,000 particles larger than 0.5 μm, and a maximum of 832,000 particles larger than 1.0 μm, per cubic meter of air.

While the ISO standard specifies the target, it does not recommend how to achieve it; the selection of specific anti-contamination measures is up to operators. Some of the common contamination prevention measures can be found in the ASHRAE guide Particulate and Gaseous Contamination in Datacom Environments.

Harms of contamination

Airborne contaminants can have a range of detrimental effects on data center equipment, depending on their composition.

Dust

All dust particles can block server air intake and exhaust. They also act as thermal insulation on server components including heatsinks, leading to thermal stress and overheating.

Dust particles can also clog up moving parts such as computer room air handler (CRAH) and computer room air conditioner (CRAC) fans and belts, causing malfunctions. They can accumulate on filters and cooling coils, reducing cooling system efficiency, and interfere with optical networking.

Conductive or insulating dust

In addition to the issues outlined above, metallic or carbon dust contamination in data centers can bridge electrical connections and trigger short circuits. This type of dust can be introduced during metal cutting, grinding or welding.

A different kind of risk is posed by electrically insulative particles, which can interfere with electrical connector contacts. Insulative particles may cause increased contact resistance or even open circuits.

Dendrites

In high humidity environments (typically understood as relative humidity above 60%), conductive dust can be created through electrochemical migration: metals such as silver, copper or tin dissolve from one conductor and deposit on a neighboring one. Just as cave stalactites build up slowly through deposition, these metals gradually form spiky, branching structures known as dendrites. Dendrites can snap off and travel through the air, potentially causing short circuits.

Zinc whiskers

Conductive particles also originate from zinc-electroplated steel. Small zinc filaments — commonly called "whiskers" — can emerge with age from older raised-floor pedestals, wire basket cable trays, or industrial shelving. These brittle filaments can easily break off and become airborne. At low voltages and currents, the energy passing through the whisker simply burns it up. But at higher voltages, vaporized metal ionizes into a highly conductive plasma arc, creating a sustained short circuit. These particles primarily threaten systems running at voltages above 48V.

Today, zinc electroplating is (mostly) avoided in data center equipment, so this issue primarily affects older facilities.

Corrosive dust

Corrosion can occur when chemically reactive dust — for example, containing sulphur or ammonium salts — or gases combine with condensation caused by high humidity and rapid temperature changes. The resulting reaction can corrode copper traces and solder joints.

Temperature and humidity are major factors that affect corrosion. The risks posed by chemically reactive contaminants increase as operators expand the temperature-humidity envelope in line with recent ASHRAE guidelines.

Corrosive gases

The presence of chlorine and hydrogen sulfide in the air accelerates copper corrosion under higher humidity conditions. If the corrosion limits are exceeded, or if there is no monitoring, ASHRAE recommends keeping relative humidity under 50% until chemical decontamination. It is important to note that corrosion from chlorine and hydrogen sulfide can, at sufficient concentrations, still reach unacceptable levels even at low relative humidity, resulting in premature IT equipment failures.

Managing contamination

Operators are advised to account for particulate contamination risks when carrying out any work in any part of the facility, and to codify measures to control contamination as part of standard operating procedures. The three elements of contamination management are monitoring, prevention and control.

Monitoring

Facilities staff should regularly examine hidden surfaces (e.g., tops of ceiling tiles, cable trays, spaces under raised floor) where particulate matter may accumulate, to get an indication of the level of contamination. They should also inspect air handling equipment to understand where and how particulate matter is being introduced.

Accurate measurements of air quality can be achieved using airborne particle counters: portable units for spot checks, and fixed-point remote units for real-time monitoring — the data from which can be fed into building management systems.

In 2021, ASHRAE expanded its thermal guidelines for data centers with recommendations for corrosive gas monitoring. Echoing prior standards, notably ANSI/ISA-71.04, ASHRAE recommends monitoring with silver and copper reactivity coupons in the data hall (the limit for silver is 200 ångström per month and for copper, 300 ångström per month).

Prevention

ASHRAE recommends that all air entering the data center is filtered with minimum efficiency reporting value (MERV) 11 to MERV 13 filters, and that white space is continuously filtered with MERV 8 filters (a higher MERV value indicates better capture of smaller particles).

Particulate filtration is often integrated into air handling systems such as CRACs. Filters must be fitted properly to avoid gaps, and must be inspected, cleaned or replaced regularly, as clogged filters can lead to reduced airflow through the system and increased fan load. Lower-than-normal air pressure at the IT racks could be an indication that air filters need to be serviced.

Special attention should be paid to air filtering in facilities equipped with air-side economizers, which are used in colder climates to save energy by bringing in fresh outside air. ASHRAE recommends a higher MERV filter rating for such facilities (e.g., MERV 14).

Humidity management also plays a part in preventing contamination-related problems. The deliquescent relative humidity of dust is the relative humidity of the air at which the dust absorbs enough moisture to become wet and conductive. The aim for facilities staff, when it comes to contaminants, is to keep the relative humidity below this level.

Contamination control mats (sometimes called sticky or tacky mats) can be deployed at entry points to remove debris from shoes and the wheels of equipment carts or dollies. These should be replaced regularly and be long enough for six steps, or about 4.6 m (15 ft).

Designated storage and staging areas outside of the white space can help avoid bringing packaging materials into a controlled environment, minimizing the risk of contamination.

Control

Even a full complement of monitoring and prevention measures will not stop the accumulation of dust — eventually, operators will have to clean their facilities. Cleaning frequency will vary depending on facility size, filter configuration, equipment density, foot traffic levels and nearby construction activity. Many facilities implement scheduled cleaning programs aligned with their maintenance cycles.

Uptime Institute recommends complete, deep cleaning of the site at least once a year. Many operators will conduct basic cleaning activities monthly, and more advanced cleaning every three to six months.

Basic cleaning can be carried out by internal data center staff, but deep cleaning is often entrusted to specialist contractors. There are no widely recognized standards for data center cleaning, so operators rely on contractors' domain knowledge.

Critical environment cleaning provider Promera (formerly Data Clean) divides data centers into five key zones:

  • Ceiling: plenum used for air distribution and power distribution.
  • Overhead: network cable trays and ductwork.
  • Equipment: exterior of servers, storage and networking hardware.
  • Top of the floor: anti-static floor surfaces and raised floor tiles.
  • Underfloor: plenum used for air distribution and power distribution.

Some operators clean all the zones at once, some alternate between above-the-floor and under-the-floor cleaning, some clean above and below with different frequency.

Data center cleaning activities are known to cause accidents and outages. As with any other work in the facility, cleaning technicians' conduct is guided by standard operating procedures that are reviewed and agreed upon by the site's managers.

Specialist equipment used for data center cleaning can include anti-static protection, specific cleaning agents, lint-free cleaning fabrics, filtered and grounded vacuum cleaners, and low-RPM floor cleaning machines that are less likely to create electromagnetic disturbances.

Prevention is better than cure

Particle accumulation in a data center occurs gradually over time, with a considerable delay before any negative effects can be observed. This means changes to operational practices that were made years ago can come back to haunt the facility. Corrosive gases may also go undetected, a risk that is particularly high in metro areas and industrial zones.

The main challenge is correctly attributing equipment problems. Sometimes, operators will be able to establish that contamination is to blame, but in other cases they might suffer mystery failures without an apparent cause. In the worst case, premature IT equipment failures may simply be accepted as normal, triggering no investigation.

The most effective approach is prevention. Best practices for contaminant management start with monitoring, followed by the development of effective contingency plans that can be rapidly implemented by operational staff in response to a contamination event. The level of data center cleanliness is an operational concern that can have a significant impact on hardware component failure rates and potentially even IT system uptime.

The Uptime Intelligence View

A dirty facility becomes less efficient, more expensive to run and subject to additional risks — including sudden equipment outages. Operators that treat contamination prevention and cleaning as key responsibilities will encounter fewer unwelcome surprises. However, cleaning poses risks too, and here the management of, and adherence to, written procedures become very important.

 

The following experts were consulted for this report:
Terry Altom, Senior Consultant, Uptime Institute
Jon DeRidder, Vice President of Technical Solutions, Promera

About the Author

Max Smolaks

Max Smolaks

Max is a Research Analyst at Uptime Institute Intelligence. Mr Smolaks’ expertise spans digital infrastructure management software, power and cooling equipment, and regulations and standards. He has 10 years’ experience as a technology journalist, reporting on innovation in IT and data center infrastructure.

Posting comments is not available for Network Guests