Over the past two decades, the data center industry has repeatedly discussed the use of direct current (DC) for power distribution — and made multiple attempts to commercialize it.
In theory, it makes sense: microelectronics run on DC. Feeding IT systems with DC power would eliminate all but one AC-DC conversion. By contrast, a typical electrical chain — using double-conversion UPS systems and standard IT power supply units (PSUs) — can have as many as five conversion steps.
Fewer active electrical components between the grid and the chips mean lower costs, reduced energy losses, and less risk of component failure. The telecom industry has long standardized on DC power distribution and has recently started adopting higher DC voltages (i.e., 336-400V) to lower distribution costs and losses. However, for most operators, the business case is not yet convincing enough to make data centers shift to DC power — although China is a notable exception.
Now the topic of DC power in data centers is back in vogue, but for different reasons: the focus is now on IT hardware performance, not facility optimization. In its push for extreme densification of compute systems, Nvidia is proposing a disaggregated IT power supply architecture centered on 800V DC (also including ±400V DC implementations) power delivery to the compute rack — and for in-rack power distribution in the future. In the first-generation of installations, DC-DC PSUs within the compute racks will step voltage down to 48V.
Nvidia's main motivation is the shift toward extremely dense racks, where PSUs would occupy valuable space that could otherwise be used for additional compute nodes. The total space needed for DC-DC power supplies is about a third or less of AC-DC PSUs. Future plans call for native 800V DC support integrated onto IT system boards, eliminating the need for dedicated rack DC-DC power supplies and freeing up even more space in compute cabinets.
Industry efforts to commercialize this architecture have accelerated since Nvidia first discussed it in 2024. At GTC San Jose 2026, the company's flagship conference held in mid-March, Uptime Intelligence counted at least eight equipment vendors showing reference designs for 800V DC power racks — power "sidecars" in industry jargon — with plans to deploy them in data halls as early as the first half of 2027.
At their core, 800V DC power racks take on most of the functionality of standard rack PSUs: they convert AC facility power (e.g., 415V AC or 480V AC) to DC while also providing isolation between the source and the load. Most vendors appear to follow similar design philosophies, producing highly modular designs in which a typical power cabinet comprises breakers and rack PDUs (for AC distribution) and multiple AC-DC power shelves, each of which contains several (e.g., three, six or nine) rectifier modules. The power shelves feed an 800V DC rack busbar that delivers power to the compute rack(s) via whips (cables) or a busway.
But there is more to power racks than simply moving AC-DC conversion out of the compute rack:
In the longer term, electrification and IT vendors appear to agree that data center power architectures will undergo more fundamental changes, beyond adding 800V DC as an option for power delivery to IT racks. The plans call for extended use of medium-voltage AC (typically 10 kV and above) distribution systems, with conversions to 800V DC (and 400/480V AC in mixed environments) occurring close to the IT load. In the immediate future, this can be achieved using a combination of large transformers and rectifiers. Ultimately, solid-state transformers, still in development, are expected to take on this role in highly integrated packages, with early commercialization anticipated from 2028-2029.
An upcoming Uptime Intelligence report will discuss potential future data center power architectures in more detail.